Directed Electronics 3100 Instrukcje Operacyjne

Przeglądaj online lub pobierz Instrukcje Operacyjne dla Alarm samochodowy Directed Electronics 3100. Directed Electronics 3100 Operating instructions Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj

Podsumowanie treści

Strona 1 - Operating Instructions

Operating InstructionsOPTISWITCH 3100 Cwith two-wire output

Strona 2 - Contents

4 Mounting4.1 General instructionsIn general, OPTISWITCH 3100 C can be mounted in anyposition. The instrument must be mounted in such a way thatthe vi

Strona 3

Warning:The housing must not be used to screw the instrument in!Applying tightening force on the housing can damage itsinternal mechanical parts.To sc

Strona 4 - 1 Sequence

20°a.b.Fig. 3: Horizontal installationa Protective sheetb Concave protective sheet for abrasive solidsIf OPTISWITCH 3100 C is mounted in the filling st

Strona 5 - 2 For your safety

In case of horizontal mounting in adhesive products, thesurfaces of the tuning fork should be vertical in order to reducebuildup on the tuning fork. O

Strona 6 - 2.6 SIL conformity

5 Connecting to power supply5.1 Preparing the connectionAlways observe the following safety instructions:l Connect only in the complete absence of lin

Strona 7 - 3 Product description

3 Remove approx. 10 cm (4 in) of the cable mantle, stripapprox. 1 cm (0.4 in) insulation from the ends of theindividual wires4 Insert the cable into t

Strona 8 - 3.3 Adjustment

14442 3Fig. 8: Material versions, single chamber housing1 Plastic (not with EExd)2 Aluminium3 Stainless steel (not with EExd)4 Filter element for pres

Strona 9 - 3.4 Storage and transport

l red - with submerged vibrating elementl green - with uncovered vibrating elementTake note of the operating instructions manual of the signalconditio

Strona 10 - 4 Mounting

6 Setup6.1 GeneralThe numbers in brackets refer to the following illustrations.On the electronics module you will find the following indicatingand adju

Strona 11 - 4.2 Mounting information

6.2 Adjustment elements51234Fig. 11: Oscillator VB 60Z - Two-wire output1 Potentiometer for switching point adaptation2 DIL switch for mode adjustment

Strona 12 - 29955-EN-060112

Contents1 About this document1.1 Function ...51.2 Target group ...51.3 Symbolism used ...

Strona 13

min.-min.detection or dry run detection) on the signalconditioning instrument.When used on a control system, the following values apply:l min. mode- V

Strona 14 - 5 Connecting to power supply

Mode on the sensor Level Signal current - Sensor Signal lamp sensorFault signal(min./max. mode)any <2.3 mAflashes redOPTISWITCH 3100 C level switch

Strona 15

7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, OPTISWITCH3100 C is completely maintenance-free.7.2 Faul

Strona 16

? Signal lamp flashes redl Electronics has detected a failureà Exchange instrument or return it for repair7.3 Exchanging the el ectronicsIn general, al

Strona 17

7 Compare the new oscillator with the old one. The type labelof the oscillator must correspond to that of the oldoscillator. This applies particularly

Strona 18 - 6.1 General

8 Dismounting8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high temp

Strona 19 - 6.2 Adjustment elements

9 Functional safety9.1 GeneralThis safety manual applies to measuring systems consisting ofOPTISWITCH 3100 C vibrating level switches and integratedos

Strona 20 - 6.3 Funct ion chart

Safety integrity of the hardware for safety-related subsystemsof type B (IEC 61508-2, 7.4.3)Safe failure fraction Hardwarefault toler-anceSFF HFT = 0

Strona 21

l The communication via the IIC bus interface is only usedfor default scaling and for service purposes.l The repair time (exchange of the measuring sy

Strona 22 - 7.2 Fault rectification

Set the mode switch on the sensor to "max"Use as overfill protec-tion systemUse as dry run pro-tection systemSafe condition "covered&quo

Strona 23 - ? Signal lamp flashes red

9 Functional safety9.1 General...279.2 Planning ...289.3 Setup ...319

Strona 24 - 7.4 Instrument repair

9.3 SetupThe prevailing plant conditions influence the safety of themeasuring system. For this reason, carefully observe themounting and installation i

Strona 25 - 8 Dismounting

This is ensured by a controlled reaching of the response heightduring filling. If filling up to the response height is not possible,then a response of t

Strona 26 - 9 Functional safety

Mode switch is set to "max"λsd49 FIT safe detected failure (1 FIT = failure/109h)λsu387 FIT safe undetected failureλdd163 FIT dangerous dete

Strona 27 - 9.2 Planning

DCS11 % Diagnosis coverage DCS= λsd/(λsd+ λsu)DCD82 % Diagnosis coverage DCD= λdd/(λdd+ λdu)TDiagnosisDiagnosis test period 100 secMTBF = MTTF + MTTR

Strona 28

PFDavgTProof= 1 yearTProof= 5 yearsTProof= 10 years< 0. 016 x 10-2< 0. 081 x 10-2< 0. 162 x 10-2PFH [1/h] < 3. 7 x 10-8/hDouble channel ar

Strona 29

PFDavgTProof= 1 yearTProof= 5 yearsTProof= 10 years< 0. 016 x 10-3< 0. 079 x 10-3< 0. 160 x 10-3PFH [1/h] < 2. 1 x 10-8/hThe time-dependen

Strona 30 - 9.5 Recurring function test

10 Supplement10.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - Thread 316L- Proces

Strona 31

Ambient conditionsAmbient temperature on the housing -40 … +80°C (-40 … +176°F)Storage and transport temperature -40 … +80°C (-40 … +176° F)Process co

Strona 32

Density- Standard >0.02 g/cm³ (>0.0007 lbs/in³)- adjustable >0.008 g/cm³ (>0.0003 lbs/in³)Electromechanical dataCable entry/plug3)- Single

Strona 33

ATEX II 1/2 DIP66 T6)6)See temperature statements in the safety instructions manualSupplementOPTISWITCH 3100 C - with two-wire output 3929955-EN-06011

Strona 34

1 About this document1.1 Funct ionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read t

Strona 35

10.2 DimensionsOPTISWITCH 3100 C7)112mm(4 13/32")117mm(4 39/64")114mm(4 31/64")~ 69mm(2 23/32")ø 77mm(3 1/32")~ 69mm(2 23/32&

Strona 36 - 10 Supplement

22mm(55/64")33mm(1 19/64")220mm (8 21/32")150mm (5 29/32")G1½Aø 43mm (1 11/16")Fig. 17: OPTISWITCH 3100 C - Threaded version

Strona 37

178mm (7 1/64")ø 34mm (1 11/32")Fig. 18: Temperature adapterSupplement42 OPTISWITCH 310 0 C - with two-wire output29955-EN-060112

Strona 38

10.3 Cer tificatesSIL declaration of conformityFig. 19: SIL declaration of conformitySupplementOPTISWITCH 3100 C - with two-wire output 4329955-EN-0601

Strona 39 - ATEX II 1/2 DIP66 T

CE declaration of conformityFig. 20: CE declaration of conformitySupplement44 OPTISWITCH 310 0 C - with two-wire output29955-EN-060112

Strona 40 - 10.2 Dimensions

Manufacturer declarationFig. 21: Manufacturer declarationSupplementOPTISWITCH 3100 C - with two-wire output 4529955-EN-060112

Strona 41

Supplement46 OPTISWITCH 310 0 C - with two-wire output29955-EN-060112

Strona 42

SupplementOPTISWITCH 3100 C - with two-wire output 4729955-EN-060112

Strona 43 - 10.3 Cer tificates

Subject to change without notice29955-EN-060112

Strona 44 - CE declaration of conformity

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained, specialist

Strona 45 - Manufacturer declaration

2.6 SIL conformityOPTISWITCH 3100 C fulfills the requirements for functionalsafety acc. to IEC 61508. You will find further information inchapter "

Strona 46

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l OPTISWITCH 3100 C level sensorl Documentation- this operating instructions ma

Strona 47

It functions even when exposed to strong external vibration orchanging products.Solid detection in waterIf OPTISWITCH 3100 C was ordered for solids de

Strona 48

3.4 Storage and transportYour instrument was protected by packaging during transport.Its capacity to handle normal loads during transport is assuredby

Komentarze do niniejszej Instrukcji

Brak uwag